Floor Heating Bypass Valve
Introduction
The Yuanlun floor heating bypass valve is a hydraulic self-acting differential pressure bypass valve for underfloor heating systems. It senses supply-return pressure difference and automatically opens a bypass passage when pressure exceeds the set value (0.05-0.15 MPa), diverting excess flow back to the return line.
Hot-forged from HPb58-2 brass with a spring-diaphragm mechanism, it requires no external power supply. Available in DN20-DN50, rated PN16, with a working temperature range of 5℃-95℃. It stabilizes system pressure, protects circulation pumps and wall-hung boilers, prevents pump overheating and boiler short-cycling, and reduces energy consumption by 10%-20% in field tests.
Key Advantages
-
Hot-Forged HPb58-2 Brass Body
Dense, porosity-free structure. Shell tested at 2.4 MPa (ISO 5208), rated PN16 (1.6 MPa). Available DN20-DN50 for residential to commercial heating projects.
-
Water Hammer Buffer & Component Protection
Cushions hydraulic shocks, reduces pressure fluctuations. Prevents circulation pump overheating and boiler short-cycling under low-flow conditions, extending equipment service life.
-
Energy Savings & Hydraulic Balance
Automatically bypasses excess flow, reducing ineffective circulation. Field tests show 10%-20% lower pump power consumption. Maintains uniform heating across all floor heating circuits.
-
All-Mechanical, Maintenance-Free
Spring-diaphragm hydraulic structure, no electronics or power supply. Natural brass body resists oxidation. No routine maintenance needed after installation and commissioning.

Technical Specifications
| Item | Specification |
|---|---|
| Body Material | Brass |
| Actuation Type | Hydraulic self‑acting (spring‑diaphragm), no power required |
| Pressure Adjustment Range | Start differential pressure: 0.05–0.15 MPa (adjustable) Max. working pressure: ≤1.0 MPa |
| Temperature Range | Medium temperature: 5 °C–95 °C Ambient temperature: –10 °C–60 °C |
| Connection Sizes | Common sizes: DN20–DN50 |
| Flow Coefficient (Kv) | Approx. 2–6 m³/h (depending on size and differential pressure) |
| Optional Features | Field‑adjustable differential pressure, integrated temperature sensor, bypass status indicator |
| Suitable Media | Water, glycol‑water solutions (≤40% concentration), and other non‑corrosive heat‑transfer fluids |
| Certifications | Complies with EN 215 (thermostatic valves) and ISO 5208 (valve testing) requirements |
Working Principle
- Pressure Sensing: Connected between supply and return lines. The spring-diaphragm mechanism continuously monitors the pressure difference.
- Automatic Bypass Opening: When differential pressure exceeds the set value (0.05-0.15 MPa), the diaphragm moves the valve core to open the bypass passage, diverting part of the flow back to the return line.
- System Balance Restoration: As bypass flow increases, total system resistance drops, restoring differential pressure below the set range. The spring returns the valve core, gradually closing the bypass.
- Low-Temperature Protection (Optional): Some models integrate a temperature sensor that increases bypass flow when return-water temperature is too low, preventing boiler condensation corrosion.
Precautions
- Install between the supply and return lines, as close to the circulation pump as possible.
- Set the differential pressure according to system design requirements (typically 0.05-0.15 MPa).
- Do not exceed max working pressure of 1.0 MPa or medium temperature of 95℃.
- Clean the pipeline before installation to remove debris that could damage the diaphragm.
- For glycol-water solutions, ensure concentration does not exceed 40%.
- The valve is maintenance-free under normal operating conditions; inspect annually for signs of seepage.
FQA
Q: Does this bypass valve require electricity?
A: No. It is fully hydraulic self-acting with a spring-diaphragm mechanism. No external power supply or electronics are needed.
Q: How do I adjust the differential pressure setting?
A: The top adjustment knob allows field adjustment of the start differential pressure within 0.05-0.15 MPa. Refer to the scale on the valve body.
Q: What size should I choose for my system?
A: Select based on system flow rate and pipe diameter. DN20-DN25 for residential systems, DN32-DN50 for commercial or large residential projects. The Kv value ranges from 2 to 6 m³/h depending on size.
Q: Can this valve be used with glycol antifreeze solutions?
A: Yes, it is compatible with glycol-water solutions up to 40% concentration, as well as water and other non-corrosive heat-transfer fluids.
Q: What is the difference between this and a manual bypass valve?
A: This valve automatically adjusts bypass flow based on real-time differential pressure, maintaining hydraulic balance without manual intervention. A manual bypass valve requires manual adjustment and cannot respond to system changes dynamically.
Q: Do you accept OEM?
A: Yes, we accept OEM and ODM orders, including custom branding, packaging and pressure ranges.